Greening'Datacenters'Through'Self4 Genera5on'of'Renewable'Energy' Thu'D.'Nguyen' Department'of'Computer'Science' ' Collaborators:'Ricardo'Bianchini,' Inigo'Goiri,'Md.'Haque,'William'Katsak,'Kien'Le' ' Mo5va5on'
Mo5va5on'
- Datacenters'consume'massive'amounts'of'energy'(electricity)'
- Vast'majority'currently'due'to'small'and'medium'scale'
datacenters'
0' 30' 60' 90'
2000' 2005' 2010' Billion'KWh/year' Electricity'consump5on'of'US'DCs'[JK’11]'
0' 30' 60' 90' 120' 150' 180' 210' 240' 270'
2000' 2005' 2010' Billion'KWh/year' Electricity'consump5on'of''WW'DCs'[JK’11]' 2%' 1.5%'
Rutgers'University' 2'
Mo5va5on'
- Electricity'comes'mostly'from'burning'fossil'fuels'
CO2'of'world4wide'DCs'[Mankoff’08]' Electricity'sources'in'US'&'WW'[DOE’10]'
100' 104' 108' 112' 116' 120'
Nigeria' Data'Centers' Czech'Rep.'
35th' 34th' MMT/year'
0%' 20%' 40%' 60%' 80%' 100%'
US' World'
Others' Renewables' Nuclear' Natural'Gas' Coal'
Rutgers'University' 3'
Can'we'use'renewables'to'reduce'this'footprint?'
- Reducing'electricity'costs'would'be'nice'too'
Outline'
- Mo5va5on:'DC'energy'usage'and'carbon'footprint'
- Reducing'carbon'footprint'&'cost'with'renewables'
- Our'target'and'research'challenges'
- Parasol:'our'solar4powered'micro4datacenter'
- GreenSwitch:'managing'power'sources'
- Previous,'current,'and'related'work'
- Conclusions'
Rutgers'University' 4'
Greening'Datacenters'
- Power'purchase'agreement,'off4site'genera5on'
– Renewable'energy'produced'at'the'best'loca5on' – Requires'transmission'
- Construc5on'of'transmission'lines'
- Energy'losses:'~15%'[IEC’07]'
- Variability'challenging'for'grid'operators'
– Example:'Google'buys'wind'power'from'NextEra'
- Self4genera5on,'co4loca5on'
– Lower'peak'power,'energy'costs'with'self4genera5on' – Loca5on'may'not'be'ideal'for'DC'or'renewable'plant' – Examples:'
- Microsoj'placed'DC'near'a'hydro'plant'in'OR'
- Apple'built'a'40MW'solar'array'in'NC'
- No'approach'is'perfect'
Rutgers'University' 5'
Self4Genera5on'Example:'Apple'NC'
Apple'DC'in'Maiden,'NC' 40MW'solar'farm'
6' Rutgers'University'
Outline'
- DC'energy'usage'and'carbon'footprint'
- Reducing'carbon'footprint'&'cost'with'renewables'
- Our'target'and'research'challenges'
- Parasol:'our'solar4powered'micro4datacenter'
- GreenSwitch:'managing'power'sources'
- Previous,'current,'and'related'work'
- Conclusions'
Rutgers'University' 7'
Our'Research'Target'
- Self4genera5on'or'co4loca5on'with'solar'and/or'wind'
– Pros:'Clean'and'available' – Cons:'Space'and'cost'
Rutgers'University' 8'
Solar'and'Wind'Are'Clean'
0' 100' 200' 300' 400' 500' 600' 700' 800' 900' 1000' g'CO2e'per'KWh'over'life5me' [Sovacool’08]'
Rutgers'University' 9'
0' 100' 200' 300' 400' 500' 600' 700' 800' 900' 1000'
Solar'and'Wind'Are'Clean'
g'CO2e'per'KWh'over'life5me' [Sovacool’08]'
Rutgers'University' 10'
Solar'More'Available'In'US'
Wind' Solar' [NREL’12]'
Fair' Good' Excellent' Outstanding' Superb'
Rutgers'University' 11'
Solar'PV'Efficiencies'Are'Increasing'
[IEA’10]' Efficiency'rates'of'PV'modules'
Rutgers'University' 12'
0' 5' 10' 15' 20' 25'
Solar'PV'Capacity'Factors'Today'
[PVOutput’12]'
Rutgers'University' 13'
Cost'of'Solar'PV'Energy'Decreasing'
Grid'electricity'prices'have'been'increasing:'30%+'since'1998'[EIA’12]'
[DOE’11,Solarbuzz’12]' 0' 4' 8' 12' 16' 20' 1985' 1987' 1989' 1991' 1993' 1995' 1997' 1999' 2001' 2003' 2005' 2007' 2009' 2011' 2013' 2015' 2017' 2019' 2021' 2023' 2025' 2027' 2029' 2011'Dollars'per'Wao'
Inverters' Panels' Installed'
Rutgers'University' 14'
0' 4' 8' 12' 16' 20' 1985' 1987' 1989' 1991' 1993' 1995' 1997' 1999' 2001' 2003' 2005' 2007' 2009' 2011' 2013' 2015' 2017' 2019' 2021' 2023' 2025' 2027' 2029' [DOE’11,Solarbuzz’12]' 2011'Dollars'per'Wao'
Inverters' Panels' Installed'
Cost'of'Solar'PV'Energy'Decreasing'
spike'in'demand' world4wide'recession' back'to'historical'levels'
Rutgers'University' 15'
0' 4' 8' 12' 16' 20' 1985' 1987' 1989' 1991' 1993' 1995' 1997' 1999' 2001' 2003' 2005' 2007' 2009' 2011' 2013' 2015' 2017' 2019' 2021' 2023' 2025' 2027' 2029' [DOE’11,Solarbuzz’12]' 2011'Dollars'per'Wao'
Inverters' Panels' Installed'
Cost'of'Solar'PV'Energy'Decreasing'
<'1/2'of'current'cost'
With'incen5ves,'the'installed'price'can'go'down'by'another'40460%'
Rutgers'University' 16'
Solar'Space'and'Cost:'Present'and'Future'
Space&as&a&factor&of&rack&area& Present& Future&(202042030)& Density'per'rack' 8kW'(200W'1U'servers)' ~47x' ~24x' 2kW'(25W'0.5U'servers)' ~12x' ~6x'
Assuming'30%'server'u5liza5on,'50%'solar'energy,'NJ'capacity'factor,'and'1'row'of'panels'
Rutgers'University' 17'
Solar'space'and'cost:'Present'and'future'
Space&as&a&factor&of&rack&area& Present& Future&(202042030)& Density'per'rack' 8kW'(200W'1U'servers)' ~47x' ~24x' 2kW'(25W'0.5U'servers)' ~12x' ~6x' Cost&per&AC&Wa:& Present& Future&(202042030)& ~$2.30' <'$1.20' Time&to&amor>ze&cost& Present& Future&(202042030)& ~12'years' <'6'years'
Assuming'30%'server'u5liza5on,'50%'solar'energy,'NJ'capacity'factor,'and'1'row'of'panels' Assuming'above'costs,'NJ'capacity'factor,'and'NJ'grid'energy'prices' Assuming'self4genera5on'and'federal'+'state'incen5ves'
Rutgers'University' 18'
Solar'space'and'cost:'Present'and'future'
Space&as&a&factor&of&rack&area& Present& Future&(202042030)& Density'per'rack' 8kW'(200W'1U'servers)' ~47x' ~24x' 2kW'(25W'0.5U'servers)' ~12x' ~6x'
Assuming'30%'server'u5liza5on,'50%'solar'energy,'NJ'capacity'factor,'and'1'row'of'panels'
Wind'takes'~12x'less'space'and'is'~3x'cheaper'
Cost&per&AC&Wa:& Present& Future&(202042030)& ~$2.30' <'$1.20' Time&to&amor>ze&cost& Present& Future&(202042030)& ~12'years' <'6'years'
Assuming'above'costs,'NJ'capacity'factor,'and'NJ'grid'energy'prices' Assuming'self4genera5on'and'federal'+'state'incen5ves'
Rutgers'University' 19'
Main'Challenge:'Power'Supply'is'Variable''
- Power'genera5on'is'variable'
– Unlikely'to'match'workload'
- Match'power'demand'and'supply'
Power' Time' Load' Variable'
20'
Solar'power' Workload' Source?' Storage?'
Rutgers'University'
Main'Challenge:'Power'Supply'is'Variable''
- Many'research'ques5ons:'
– What'kinds'of'DC'workloads'are'amenable?' – What'kinds'of'techniques'can'we'apply?' – How'well'can'we'predict'solar'energy'availability?' – If'baoeries'are'available,'how'should'we'manage'them?' – Can'we'leverage'geographical'distribu5on?'
- Building'hardware'&'sojware'to'answer'ques5ons'
Rutgers'University' 21'
Outline'
- DC'energy'usage'and'carbon'footprint'
- Reducing'carbon'footprint'&'cost'with'renewables'
- Our'target'and'research'challenges'
- Parasol:'our'solar4powered'micro4datacenter'
- GreenSwitch:'managing'power'sources'
- Previous,'current,'and'related'work'
- Conclusions'
Rutgers'University' 22'
The'Rutgers'Parasol'Project'
Rutgers'University' 23'
Parasol:'Our'Hardware'Prototype'
- Unique'research'plarorm'
– Solar4powered'compu5ng' – Remote'DC'deployments' – Sojware'to'exploit'renewables'within'and'across'DCs' – Tradeoff'between'renewables,'baoeries,'and'grid'energy' – Free'cooling,'wimpy'servers,'solid4state'drives'
Rutgers'University' 24'
Parasol:'Our'Hardware'Prototype'
Rutgers'University' 25'
Parasol'Details'
- Steel'structure'on'the'roof'
– 16'solar'panels:'3.2'kW'peak' – Container'hosts'2'racks'of'IT'
- Backup'power'
– Baoeries:'32kWh' – Grid'
- IT'equipment'
– 64'Atom'servers'(so'far):'1.9'kW' – 2'switches'
- Cooling'
– Free'cooling:'10'−'400'W' – Air'condi5oning:'2'kW'
Rutgers'University' 26'
Electrical'infrastructure'
Charge' Controller' Inverter' Electrical' Panel' DC' AC' AC' DC' AC' Power'grid' AC'
27'
IT'Equipment'
Rutgers'University'
Outline'
- DC'energy'usage'and'carbon'footprint'
- Reducing'carbon'footprint'&'cost'with'renewables'
- Our'target'and'research'challenges'
- Parasol:'our'solar4powered'micro4datacenter'
- GreenSwitch:'managing'power'sources'
- Previous,'current,'and'related'work'
- Conclusions'
Rutgers'University' 28'
Example'Energy'Source'Management'
Charge' Controller' Inverter' Electrical' Panel' DC' AC' AC' DC' AC' Power'grid' AC' Time' Power'
29'
IT'Equipment'
Rutgers'University'
Example'Energy'Source'Management'
Charge' Controller' Inverter' Electrical' Panel' DC' AC' AC' DC' AC' Power'grid' AC' Time' Power'
30'
IT'Equipment'
Rutgers'University'
Example'Energy'Source'Management'
Charge' Controller' Inverter' Electrical' Panel' DC' AC' AC' DC' AC' Power'grid' AC' Time' Power'
31'
IT'Equipment'
Rutgers'University'
Possible'Energy'Source'Management'
Power' Time'
Basic'
32' Rutgers'University'
GreenSwitch'
- Minimize'brown'electricity'cost'
– Brown'energy' – Peak'brown'power' – Baoery'life5me'constraint'
- Manage'energy'sources'
– Use'solar/net'metering' – Charge/discharge'baoery' – Limit'brown'peak'power'
- Manage'workload'
– Turn'servers'on/off' – Delay'deferrable'jobs'
Parasol' GreenSwitch'
Perform'changes' Get'status'
33' Rutgers'University'
GreenSwitch'
GreenSwitch'Architecture'
Predictor' Baoery' Charge'Level' Workload' Predic5on' Energy' Availability' Predic5on' Solver' Energy'Source' Schedule' Workload' Schedule' Configurer'
Parasol'
Time' Power' Brown' Price' Solar' Time' Power' Workload' Use'solar'to'power'all'servers' Charge'baoery'with'surplus'solar' Workload' Model'&' MILP'
34' Rutgers'University'
Experimental'Environment'
- Evalua5on'on'64'Parasol'nodes'
– 12'one4day'experiments' – Deferrable'vs.'non4deferrable'workloads' – Baseline'datacenter'(no'solar,'no'baoeries,'no'delays)'
- New'Jersey'brown'electricity'pricing'
– On/off4peak'energy,'peak'power,'net'metering'
- GreenSwitch'for'Hadoop'(configurer)'
35' Rutgers'University'
Experimental'Environment'
36'
SWIM:'Facebook'based'workload'[MASCOTS’11]'
IT'load'
Rutgers'University'
Parasol'Without'GreenSwitch'
Green'use' Green'available' Net'metering' Brown'use' IT'load'
66%'cost'savings'→'Solar'amor5zed'in'7'years'
37' Rutgers'University'
GreenSwitch:'Non4Deferrable'Workload'
Baoery'discharge' Baoery'charge' IT'load'
75%'cost'savings'→'Baoeries'cannot'be'amor5zed'
Peak'grid'power'
38'
Green'use' Brown'use' Green'available'
Rutgers'University'
GreenSwitch:'Deferrable'Workload'
Baoery'discharge' Baoery'charge' IT'load' Net'metering'
96%'cost'savings'→'Solar'+'baoeries'amor5zed'in'7.6'years''
39'
Green'available' Green'use'
Rutgers'University'
Parasol:'A'Real'System'
- Real'sojware'running'on'real'hardware'
- Power'losses'
- Overhead'of'energy'source'switching'
- System'limita5ons'
– Net'metering'vs.'baoery'charging' – Use'grid'vs.'net'metering' – Green'baoery'charging'vs.'use'grid'
Rutgers'University' 40'
Outline'
- DC'energy'usage'and'carbon'footprint'
- Reducing'carbon'footprint'&'cost'with'renewables'
- Our'target'and'research'challenges'
- Parasol:'our'solar4powered'micro4datacenter'
- GreenSwitch:'managing'power'sources'
- Previous,'current,'and'related'work'
- Conclusions'
Rutgers'University' 41'
Other'Works'on'Green'DC'Sojware'
- Follow'the'renewables'[HotPower’09,'IGCC’10]'
- Delay'batch'jobs'while'respec5ng'deadlines'[SC’11,'
Eurosys’12]'
- Power'source'management'[SustainIT’12,'
ASPLOS’13]'
- Green'SLAs'in'HPC'clouds'[IGCC’13]'
Rutgers'University' 42'
Current'Works'
- Temperature4'and'varia5on4aware'management'of'
free4cooled'datacenters'
- DC'placement'world4wide'for'cost4effec5ve'follow4
the4renewables'
- Matching'power'demand'to'power'supply'for'non4
deferrable'workloads'
– Trading4off'response'5me'and'durability'for' interac5ve'workloads'(GreenCassandra)'
Rutgers'University' 43'
Related'Work'
- Blink,'UMass,'Amherst'
- Algorithms'for'Sustainable'IT,'Caltech'
- Sustainable'datacenters,'HP'Labs''
- Ren'et'al.,'MASCOTS'2012'
- Li'et'al.,'ISCA'2012'
Rutgers'University' 44'
Conclusions'
- Greening'datacenters'
– Challenges'&'opportuni5es' – Hardware/sojware'solu5on'
- GreenSwitch'benefits'
– Delaying'load'and'solar'gives'the'best'results' – Reduces'amor5za5on'5me'by'1.842x' – Flexibility:'no'baoeries,'workloads,'wind'…'