Technical Training 2007 Technical Training 2007 Technical Training 2007
Product Features Technical Training 2007 Technical Training 2007 - - PowerPoint PPT Presentation
Product Features Technical Training 2007 Technical Training 2007 - - PowerPoint PPT Presentation
Product Features Technical Training 2007 Technical Training 2007 Technical Training 2007 Product Features Less foot print occupied Less space required. Technical Training 2007 Technical Training 2007 Technical Training 2007 Product
Technical Training 2007 Technical Training 2007 Technical Training 2007
Product Features
- Less foot print occupied
- Less space required.
Technical Training 2007 Technical Training 2007 Technical Training 2007
Product Features
- Made of AISI 316 Stainless Steel
- High heat exchange efficiency
Technical Training 2007 Technical Training 2007 Technical Training 2007
Conventional Back to Back Circuits BPHE
Primary Circuit 1 Primary Circuit 2
Secondary Circuit
Primary Circuit 1 Primary Circuit 2
Inverter Mini Chiller True Dual Circuits BPHE
New Technology BPHE- True Dual Circuits
Product Features
Technical Training 2007 Technical Training 2007 Technical Training 2007
Product Features
- Support up to 50 chiller and 120 fan coil units
through chiller bus
Technical Training 2007 Technical Training 2007 Technical Training 2007
Product Features
- A network up to 50 chillers
- Operation control on chillers done
through microprocessor controller.
- Additional chiller can be added on by just
extend the water piping.
Water In Water Out
Chille r Bus Up to 50 Chille r s
Technical Training 2007 Technical Training 2007 Technical Training 2007
Product Features
- Can be done through Chiller Control
Panel
- User friendly and versatile controls
- Main menu includes:
Ope r ation T ime r Display Se tting Alar m
- Whole system configuration
- Unique system configuration
Technical Training 2007 Technical Training 2007 Technical Training 2007
Product Features
- 1. Less Start & Stop
- 2. Fast Cooling/ Heating
- 4. Low Starting Surge
- 3. Precise Temperature Control
Running current Hours of operation Running current Hours of operation Conventional air conditioner:
- High starting current
- Frequent on/off cycle
Inverter air c onditioner:
- L
- w starting c urrent
- Smooth operation
Inverter air c onditioner:
- L
- w starting c urrent
- Smooth operation
Technical Training 2007 Technical Training 2007 Technical Training 2007
Product Features
Conventional System Inverter System
Technical Training 2007 Technical Training 2007 Technical Training 2007
Product Features
- High & Low Pressure Switches
- Anti Freeze Protection Sensor
- Discharge Temperature Sensor
- Over Pressure Relief Valve
- Water Pressure Differential Switch
- Anti Freeze Heater on BPHE
- Compressor, Water Pump Overload Protector
Back To Co Back To Content ntent
Technical Training 2007 Technical Training 2007 Technical Training 2007
Schematic Diagram & Components
Technical Training 2007 Technical Training 2007 Technical Training 2007
Schematic diagram
Condenser Coil 1 Acc Acc Liq Rvr Liq Rvr BPHE FS Condenser Coil 2 Disch Temp 2 (Disch Comp 2) Disch Temp 1 (Disch Comp 1) Inv Comp Std Comp Suct Temp (Suction) HP1 HP2 LP2 LP1 Cond In Temp 1 (Condenser) Cond Out Temp 1 (Def Comp 1) BPHE Out Temp (BPHE Out) BPHE In Temp (BPHE In) EWT (Water In) LWT (Water Out) Pump Cond Out Temp 2 (Def Comp 2) Filter Drier Heating Cap Tube Check valve Cooling Cap Tube Check valve Filter Drier EXV O/A Temp (Outdoor Air) Summary Pages- Screen 3 Display Menu- Defrost Sensor Display Menu- Inverter Chiller Display Menu- Discharge Sensor
5ACV100CR 4WV 4WV
Technical Training 2007 Technical Training 2007 Technical Training 2007
Components
Variable speed fan motors (100% , 70% & 50% ) Heat exchangers with gold fin as standard Water pump True dual circuits BPHE (Brazed plate heat exchanger) Expansion tank ( 8L) Control box assembly Coil guards Fan guards
Technical Training 2007 Technical Training 2007 Technical Training 2007
Components
I PM board
(I ntelligent power module)
Main board Magnetic contactors EMI filter Capacitor board PFC capacitor
(Power factor correction)
Uni- directional bridge diode 3 phase rectifier bridge diode Fan capacitors Power board
Technical Training 2007 Technical Training 2007 Technical Training 2007
Components
For Model 55, 75, 100 & 135 For Model 30
Technical Training 2007 Technical Training 2007 Technical Training 2007
Components
- To convert rectified DC current
+500VDC to respective desired voltages
- 12VDC relay
- MCU +5VDC
- IPM +15VDC
- Ensure stability of above voltages
within power supply voltage fluctuation range (304-480 VAC)
- Over voltage feedback
- Output short circuit protection
Technical Training 2007 Technical Training 2007 Technical Training 2007
Components
Technical Training 2007 Technical Training 2007 Technical Training 2007
Components
Technical Training 2007 Technical Training 2007 Technical Training 2007
Components
Variable drive system compartment Fixed drive system compartment
High pressure switch (NC) 600 psi – open, 480psi – close. Low pressure switch (NC) 18 psi – open, 28 psi – close. Pump OLP (overload protector) Differential pressure switch Over pressure relief valve Anti freeze heater on BPHE Compressor OLP (overload protector)
Chiller panel controller Fixed speed scroll compressor (R410A) Variable speed scroll compressor (R410A)
EXV (Electronics expansion valve
4 Way valve
Technical Training 2007 Technical Training 2007 Technical Training 2007
Installation & Commissioning
Technical Training 2007 Technical Training 2007 Technical Training 2007
Installation & Commissioning
- Unit Handling
- Unit Placement
- Maintenance Access
- Water Piping & Fitting
- Power Supply & Electrical Connection
- Preliminary Checking before Start-up
- General Control Flow Chart
Technical Training 2007 Technical Training 2007 Technical Training 2007
5ACV 100/135/210 CR
Installation & Commissioning
Technical Training 2007 Technical Training 2007 Technical Training 2007
- Air Cooled Chiller are cooled by air, space restriction will reduces the
air flow, decrease the cooling capacity, increase the power input and, in come cases, prevent the unit from operating because of an excess
- f condensation pressure.
- 5ACV equipped with propeller fan, which doesn’t need ductwork on fan
- utlet.
- Direct effect of the wind on the discharge surface of the fan should be
avoided.
- Enough clearance around the unit for maintenance works.
Installation & Commissioning
Technical Training 2007 Technical Training 2007 Technical Training 2007
- Minimum clearances
5ACV100/135/210CR 5ACV30/55/75CR
Installation & Commissioning
Technical Training 2007 Technical Training 2007 Technical Training 2007
Installation & Commissioning
Technical Training 2007 Technical Training 2007 Technical Training 2007
5ACV 30 / 55 / 75 CR
Installation & Commissioning
Technical Training 2007 Technical Training 2007 Technical Training 2007
Installation & Commissioning
5ACV 100 / 135 CR
Technical Training 2007 Technical Training 2007 Technical Training 2007
5ACV 210 CR
Installation & Commissioning
Technical Training 2007 Technical Training 2007 Technical Training 2007 Install piping with minimum bends and changes in elevation to minimize pressure drop. Consider the following:
!
- Vibration eliminators to reduce vibration and noise transmission
to the building.
- Shut off valves to isolate the unit from the piping system during
unit servicing.
- Manual or automatic air vent valves at the highest points of the
chilled water piping.
- A means of maintaining adequate system water pressure
(expansion tank or regulating valve)
- Temperature and pressure indicators located at the unit to air in
unit servicing.
Installation & Commissioning
Technical Training 2007 Technical Training 2007 Technical Training 2007
Water connection could be damaged by an excessive stress when screwing them. Use a second spanner to compensate the stress of tightening.
- Safety differential pressure switch is used to ensure
adequate water flow to evaporator before starting up the unit.
- Balancing valve to regulate the amount of water flow rate
through the unit.
It is mandatory to install a strainer at the inlet of the unit.
Installation & Commissioning
! !
Technical Training 2007 Technical Training 2007 Technical Training 2007
Recommended Piping Connection
Installation & Commissioning
Technical Training 2007 Technical Training 2007 Technical Training 2007
Recommended Fuses & Cable Size
10 5 10 5 10 3 Power Supply Cable Size (mm2) * Number of Conductor 1.5 1.5 1.5 Interconnection Cable Size (mm2) * 10 25 36 Recommended Fuse (A) * 415 / 3 / 50 415 / 3 / 50 230 / 1 / 50 Voltage Range ** 5ACV75CR 5ACV55CR 5ACV30CR Model 10 5 10 5 10 3 Power Supply Cable Size (mm2) * Number of Conductor 1.5 1.5 1.5 Interconnection Cable Size (mm2) * 100 60 40 Recommended Fuse (A) * 380 – 415 / 3 / 50 Voltage Range ** 5ACV210CR 5ACV135CR 5ACV100CR Model
IMPORTANT:
- The figures shown in the table are for information purpose only. They should be checked and selected to comply
with local/national codes of regulation. This is also subject to the type of installation and conduction used. * The appropriate voltage range should be checked with label data on the unit.
Installation & Commissioning
Technical Training 2007 Technical Training 2007 Technical Training 2007 Before carrying out any operations on the electrical system, make sure that the unit is de-energized.
!
It is important that the appliance is grounded.
!
Before connecting the power supply lines, check that the available voltage value does not exceed the range specified in the electrical data being provided in Installation Manual.
!
It’s recommended to check the correct sequence of the 3 supply phases R-S-T before the unit start up.
!
Installation & Commissioning
Technical Training 2007 Technical Training 2007 Technical Training 2007
- Check the power supply and grounding cable.
- Check that any voltage and phase variation in the power supply does
not exceed the prefixed thresholds.
- Check that components of the external water circuit have been
installed properly, and according to the manufacturer’s instructions.
- Check that the filling of the hydraulic circuits, and make sure that the
fluid circulation is correct, without any trace of leaks and air bubbles.
- Check that the direction of rotation of the pumps is correct.
- Adjust the liquid distribution network in such a way that the flow rate
is within the specified range.
- Check that the water quality is up to the specification.
Installation & Commissioning
Technical Training 2007 Technical Training 2007 Technical Training 2007
Start No Stop Inverter Comp Yes Stop pump 60s
Clash between current & selected mode of operation?
Cooling mode No Heating? No Yes Yes Heating mode System On? Yes Cooling? No
Installation & Commissioning
Technical Training 2007 Technical Training 2007 Technical Training 2007
Cooling Mode Control Flow Chart
Start No Stop Inverter Comp ΔT < -2°C for > 180s? 30s
Frequency & EXV opening adjustment
No Pump on No Yes Return No Yes Yes Yes Yes No 5s ΔT > -2°C ?
Shut Inverter 4WV & start Inverter O/Fan
Start Inverter Comp ΔT > 2°C ? Inverter Comp Off? Pump on for >3 min? ΔT = Actual Entering water temp - Cooling water temp set point
Installation & Commissioning
Technical Training 2007 Technical Training 2007 Technical Training 2007
Heating Mode Control Flow Chart
Start No Stop Inverter Comp ΔT < -2°C for > 180s? 30s
Frequency & EXV opening adjustment
No Pump on No Yes Return No Yes Yes Yes Yes No 5s ΔT > -2°C ? Shut Inverter 4WV & start Inverter O/Fan Start Inverter Comp ΔT > 2°C ? Inverter Comp Off? Pump on for >3 min? ΔT = Heating water temp set point - Actual Entering water temp
Installation & Commissioning
Back To Co Back To Content ntent
Technical Training 2007 Technical Training 2007 Technical Training 2007
Self Diagnosis & Troubleshooting
Technical Training 2007 Technical Training 2007 Technical Training 2007
Error Code
Self Diagnosis & Troubleshooting
OFF OFF OFF OFF OFF Manual Wrong phase Sequencing Phase Seq Error OFF OFF OFF OFF OFF Auto EEPROM read/write error Memory Error OFF OFF OFF OFF OFF Auto IPM over-current or over heat IPM Error OFF Pump Control Measure OFF Comp System 1 (Variable Drive) OFF Fan OFF Comp System 2 (Fixed Drive) OFF Manual Phase Missing Phase Missing Fan Reset (default) Error Description Error Display
Continue….
Technical Training 2007 Technical Training 2007 Technical Training 2007
Self Diagnosis & Troubleshooting
- OFF
OFF
- Auto
Coil in system 1 sensor error Coil 1 inlet Temp Open/Short OFF OFF OFF OFF OFF Auto BPHE water out sensor error Leaving Water Sensor Open/Short
- OFF
OFF
- Auto
BPHE refrigerant in sensor error V-Hx inlet Temp sensor Open/Short
- OFF
OFF
- Auto
BPHE refrigerant
- ut sensor error
V-Hx outlet Temp sensor Open/Short OFF OFF Pump Control Measure OFF OFF Comp System 1 (Variable Drive) OFF OFF Fan OFF OFF Comp System 2 (Fixed Drive) OFF Auto BPHE water in sensor error Entering Water Sensor Open/Short OFF Auto Ambient Temp sensor error Outdoor Air Sensor Open/Short Fan Reset (default) Error Description Error Display
Error Code
Continue….
Technical Training 2007 Technical Training 2007 Technical Training 2007
Self Diagnosis & Troubleshooting
OFF OFF
- Auto
Comp 1 Overload Comp 2 Overload
- OFF
OFF
- Auto
Comp 1 Overload Comp 1 Overload OFF OFF OFF OFF OFF Auto Leaving water temp too low Cool Mode Antifreeze OFF OFF OFF OFF OFF Auto Pump OLP
- pened
Pump overload OFF Pump Control Measure OFF Comp System 1 (Variable Drive) OFF Fan OFF Comp System 2 (Fixed Drive) OFF Manual Cv Contact
- pened
Water Flow Error Fan Reset (default) Error Description Error Display
Error Code
Continue….
Technical Training 2007 Technical Training 2007 Technical Training 2007
Self Diagnosis & Troubleshooting
OFF OFF
- Auto
Coil out system 2 sensor error Comp 2 Defrost sensor Open/Short OFF OFF
- Auto
Discharge comp system 2 sensor error Comp 2 Discharge Sensor Open/Short/Overheat
- OFF
OFF
- Auto
Discharge Comp system 1 sensor error Comp 1 Discharge Sensor Open/Short
- OFF
OFF
- Auto
Comp 1 discharge Overheat Comp 1 Discharge Overheat
- OFF
OFF
- Auto
Coil Out system 1 sensor error Comp 1 Defrost Sensor Open/Short
- OFF
OFF
- Auto
Suction comp system 1 sensor error Comp 1 Suct Sensor Open/Short Pump Control Measure Comp System 1 (Variable Drive) Fan Comp System 2 (Fixed Drive) Fan Reset (default) Error Description Error Display
Error Code
Continue….
Technical Training 2007 Technical Training 2007 Technical Training 2007
Self Diagnosis & Troubleshooting
OFF OFF
- Auto
System 2 high pressure High Pressure 2 OFF OFF
- Auto
System 2 low pressure Low Pressure 2
- OFF
OFF
- Auto
System 1 low pressure Low Pressure 1 OFF OFF OFF OFF OFF <460V, Auto
- Comp. High Voltage
(>490V) OV/UN Voltage OFF OFF OFF OFF OFF >340V, Auto
- Comp. Low Voltage
(<310V) OV/UN Voltage
- OFF
OFF
- Auto
System 1 high pressure High Pressure 1 Pump Control Measure Comp System 1 (Variable Drive) Fan Comp System 2 (Fixed Drive) Fan Reset (default) Error Description Error Display
Error Code
Technical Training 2007 Technical Training 2007 Technical Training 2007
- 1. No response after power-on
No response Check setting &
- perating
condition Check Input power supply vac Change Power Board Is Power Board OK? Is main board LED light? Is R,S,T Input voltage normal? Yes No Yes No No
Self Diagnosis & Troubleshooting
Main Board or IPM Board Faulty Is connection IPM and Main Board OK? Yes No Yes Connection Wire or Connector Faulty Rectifier Main Board IPM Power Board
Technical Training 2007 Technical Training 2007 Technical Training 2007
- 2. LED on main board normal, but no output.
LED lighted, No output Is Setting Parameter ok? No Is Operating Condition OK? Is main board’s fuse ok? Replace main board Change the Setting Parameter Check Operating condition Change Fuse No No Yes Yes
Self Diagnosis & Troubleshooting
Yes
Technical Training 2007 Technical Training 2007 Technical Training 2007
- 3. Other functions normal but compressor not functioning
Self Diagnosis & Troubleshooting
Others OK, Comp not functioning Is fuse in DC loop ok? Yes Is IPM OK? Is compressor
- k?
Change Fuse Check operating conditions Check IPM No No Yes No Replace Compressor Yes
Technical Training 2007 Technical Training 2007 Technical Training 2007
- 4. Flow switch protection -E01
Water flow error Short JK4 Is water flow error persists? Main board faulty , replace main board Flow switch faulty or pump stopped. No Yes JK4 on main board
Self Diagnosis & Troubleshooting
Technical Training 2007 Technical Training 2007 Technical Training 2007
- 5. Over voltage protection -E02
OV/UN Voltage Is Power supply < 460VAC? Power board error, rectify. Check the Electrical supply Yes Is Power supply > 490VAC? No No Yes
Self Diagnosis & Troubleshooting
Technical Training 2007 Technical Training 2007 Technical Training 2007
- 6. Under voltage protection -E03
OV/UN Voltage Is Power supply > 340VAC? Power board error, rectify. Check the Power supply Yes Is Power supply < 310VAC? No No Yes
Self Diagnosis & Troubleshooting
Technical Training 2007 Technical Training 2007 Technical Training 2007
- 7. Pump overload protection- E05
Pump overload Remove JK8, 97 & 98, check connectivity Pump overload Main board faulty No Is voltage of 97, 98 on heat relay VDC = 0 V Yes No Yes JK8 on main board
Self Diagnosis & Troubleshooting
Technical Training 2007 Technical Training 2007 Technical Training 2007
- 8. Phase missing – E06
Phase missing Is Voltage between R,S,T 415VAC ±20%? No Is J-RST on main board 415VAC ±20%? Disconnect power, remove J-RST, is voltage of socket 415VAC ±20%? To Check/replace EMI filter Check incoming supply Main board faulty Yes No No Yes Yes 3 Phase supply
Self Diagnosis & Troubleshooting
Technical Training 2007 Technical Training 2007 Technical Training 2007 Phase seq error – E07
Self Diagnosis & Troubleshooting
- Interchange any 2 phase of R, S, T.
Memory Error – E08
- Replace chip 24C02
Sensor Error – E09, E12, E14, E20, E21, E22, E23, E24, E25, E30, E31, E33, E34
- Check against the resistance cable.
Technical Training 2007 Technical Training 2007 Technical Training 2007
- 9. IPM protection –E15
IPM Error Replace Check compressor Normal Is IPM Error persists? Is IPM ok? Is current at rated frequency
- k?
Yes No Yes No No
Self Diagnosis & Troubleshooting
Inverter Chiller Comp Freq : 75Hz EXV : 320 Comp Amp : 9.7A DC Bus : 555V
Display Menu for Inverter
Technical Training 2007 Technical Training 2007 Technical Training 2007
Yes Is IPM temperature >100°C? Rectify Main board faulty
- r wrong signal
Is heat sink temperature >100°C? No Reapply heat compound No Yes No Is heat compound dried
- ut?
Change IPM Yes Yes
- Use thermocouple.
- Use thermocouple.
- 9. IPM protection –E15
Self Diagnosis & Troubleshooting
Heat Sink Heat Compound IPM
Technical Training 2007 Technical Training 2007 Technical Training 2007
- 10. Variable compressor over-current protection –E16
Comp 1
- verload
Main board or compressor faulty Replace Check Compressor winding resistance Yes
- Restart. Check
compressor current on the handset. < 18 A? No
Self Diagnosis & Troubleshooting
* For 5ACV30CR, Overload protection triggers when compressor current > 27 A
Technical Training 2007 Technical Training 2007 Technical Training 2007
- 11. Variable drive high pressure protection –E17 & E27
High Pressure 1 Check AC system for overload Rectify Replace No Is high pressure switch ok? Yes
Self Diagnosis & Troubleshooting
- Remove hp pin from main board.
- Remove OF.
Technical Training 2007 Technical Training 2007 Technical Training 2007
- 12. Variable drive low pressure protection –E18 & E28
Low Pressure 1 Check AC system for low pressure Rectify Replace No Is low pressure switch ok? Yes
Self Diagnosis & Troubleshooting
Technical Training 2007 Technical Training 2007 Technical Training 2007
- 13. Variable compressor high discharge temperature protection
Comp 1 Discharge Overheat Temp sensor ok? (<100°C?) Rectify Compressor stops Yes > 110 °C ? No Check AC system Replace
Self Diagnosis & Troubleshooting
Technical Training 2007 Technical Training 2007 Technical Training 2007
- 14. Fixed compressor over-current protection
Comp 2 Overload Check on compressor winding resistance, is it to spec ? No Check on Compressor insulation, is it
- k?
Check current reading on handset against actual reading, is it very big different? Current sensing circuit
- error. Replace main
board Rectify Rectify Normal No Yes No Is supply voltage ok? Rectify No Yes Yes Yes
Self Diagnosis & Troubleshooting
- Check continuity.
- Check VAC
- Check continuity.
Technical Training 2007 Technical Training 2007 Technical Training 2007
Power Board Checking
Check bridge diode Is Power board DC-IN voltage normal? No Is JP-power/DC- OUT output normal? Yes Replace power Board No Yes
Self Diagnosis & Troubleshooting
Power Board Checking DC-IN (+590VDC) JP-Power (+12Vdc & 7Vdc) DC-Out (+15Vdc) Main Board or IPM Board Faulty Power Board
Technical Training 2007 Technical Training 2007 Technical Training 2007
IPM Board Checking
Self Diagnosis & Troubleshooting
P N
Use multi-meter to check the Vdc between the P and N. The voltage should be around 590Vdc
Technical Training 2007 Technical Training 2007 Technical Training 2007
Power Supply Checking
- Use the multi-meter to check the power supply to controller.
- Refer to any of the 2 phase of supply (R&S, S&T or R&T).
- The supply should be 415VAC
Self Diagnosis & Troubleshooting
Technical Training 2007 Technical Training 2007 Technical Training 2007
Fuse Checking
Use multi-meter to check the continuity of the fuse. Fuse with sound ‘BEEP’ is ok
Self Diagnosis & Troubleshooting
Technical Training 2007 Technical Training 2007 Technical Training 2007
Fuse Checking
Use multi-meter to check the continuity of the fuse. Fuse with sound ‘BEEP’ is ok
Self Diagnosis & Troubleshooting
Technical Training 2007 Technical Training 2007 Technical Training 2007
Check Compressor Check on compressor winding resistance, is it ok? No Check on Compressor insulation, is it
- k?
Change Compressor No Yes Yes Is compressor short body? Yes No Compressor OK Change Compressor Change Compressor
Compressor Checking
Self Diagnosis & Troubleshooting
Technical Training 2007 Technical Training 2007 Technical Training 2007 + ~ ~
- Use multi-meter to check the continuity of
the bridge diode.
Bridge Diode Checking
Self Diagnosis & Troubleshooting
Technical Training 2007 Technical Training 2007 Technical Training 2007
9.99 8 9.17 10 8.43 12 7.76 14 7.15 16 10.89 6 11.88 4 12.99 2 14.21 15.56
- 2
17.06
- 4
18.73
- 6
Resistance (k Ω) Temperature (°C)
Low Temperature Sensor (Coil sensor and room/ambient sensor)
3.84 32 3.56 34 3.31 36 3.08 38 2.87 40 4.13 30 4.46 28 4.81 26 5.20 24 5.62 22 6.08 20 6.59 18 Resistance (k Ω) Temperature (°C)
Resistance Table
When Temp = 25°C, Resistance = 5 kΩ
Technical Training 2007 Technical Training 2007 Technical Training 2007
221.86 8 201.16 10 182.60 12 165.95 14 150.98 16 245.00 6 279.90 4 299.94 2 332.55 369.25
- 2
410.63
- 4
457.41
- 6
Resistance (k Ω) Temperature (°C)
High Temperature Sensor (Discharge sensor)
73.67 32 67.66 34 62.21 36 57.24 38 52.73 40 80.30 30 87.60 28 95.67 26 104.59 24 114.46 22 125.40 20 137.52 18 Resistance (k Ω) Temperature (°C)
Resistance Table
When Temp = 100°C, Resistance = 6.5 kΩ
Back To Co Back To Content ntent
Technical Training 2007 Technical Training 2007 Technical Training 2007
Centralized Control Solution: Smart Manager
Technical Training 2007 Technical Training 2007 Technical Training 2007
Smart Manager
- Support up to 50
Support up to 50 Chillers in one Chillers in one chiller BUS and up chiller BUS and up to 120 to 120 FCUs FCUs in one in one NIM BUS. NIM BUS.
Mini Chiller Mini Chiller Mini Chiller FCU FCU FCU
Chiller Panel Controller Chiller Panel Controller Chiller Panel Controller
Nim
Netware 2/ SLM3 or wireless controller
Nim Nim
Netware 2/ SLM3 wireless controller Netware 2/ SLM3
- r wireless
controller
Can Support Up Can Support Up to 50 Chillers to 50 Chillers On the C BUS On the C BUS Can Support up to Can Support up to 120 120 FCUs FCUs On the On the NIM BUS NIM BUS
Smart Manager Smart Manager
Technical Training 2007 Technical Training 2007 Technical Training 2007
Smart Manager
Programmable Energy Saving Timer Programmable Energy Saving Timer
- Chiller
Chiller – – One set of 7 days programmable operating schedules One set of 7 days programmable operating schedules (2 ON/OFF timers per day) (2 ON/OFF timers per day)
- FCUs
FCUs – – Five set of 7 days programmable operating schedules. Five set of 7 days programmable operating schedules. (2 ON/OFF timers per day) (2 ON/OFF timers per day)
Technical Training 2007 Technical Training 2007 Technical Training 2007
Smart Manager
- 10
10 holidays with duration of
holidays with duration of 99
99 days each can be set. All
days each can be set. All FCUs FCUs & Chiller will be turned OFF during the holiday & Chiller will be turned OFF during the holiday period. period.
- Timer Schedules are disabled during holiday period.
Timer Schedules are disabled during holiday period.
Holiday Setting (FCU) Holiday Setting (FCU)
Technical Training 2007 Technical Training 2007 Technical Training 2007
Smart Manager
Whenever Smart Manager receives a new alarm from Chiller Whenever Smart Manager receives a new alarm from Chiller
- r
- r FCUs
FCUs, an alarm message will pop up on the LCD screen; , an alarm message will pop up on the LCD screen; shows type of alarm, alarm occurred time, date and unit. shows type of alarm, alarm occurred time, date and unit. Backlight blinking and alarms buzzer produces beeping Backlight blinking and alarms buzzer produces beeping sound (if it sound (if it’ ’s set s set ‘ ‘ON ON’ ’) )
Display up to 46 types of Chiller Fault/ Alarm and 6 Display up to 46 types of Chiller Fault/ Alarm and 6 types of types of FCUs FCUs Fault/ Alarm Fault/ Alarm
New Alarm 1 Comp 1 Overload 06/04/05 12:00 am [Ch 3]
Technical Training 2007 Technical Training 2007 Technical Training 2007
Smart Manager
Memory Backup, Alarm Memory for Chiller & Memory Backup, Alarm Memory for Chiller & FCUs FCUs Real Time Clock (RTC) Settings Real Time Clock (RTC) Settings
- Allows user to set the time and date
Allows user to set the time and date
Password Protection Password Protection
- For advance parameter settings (Chiller)
For advance parameter settings (Chiller)
- Setting Protection
Setting Protection
Technical Training 2007 Technical Training 2007 Technical Training 2007
Smart Manager
Defrost & Discharge Sensor Temp Display (Chiller) Defrost & Discharge Sensor Temp Display (Chiller) Accumulative Compressor Run Time Accumulative Compressor Run Time
- For servicing purpose
For servicing purpose
Defrost Sensor Comp 1 : 12.8 °C Discharge Sensor Comp 1 : 36.5 °C
Technical Training 2007 Technical Training 2007 Technical Training 2007
Smart Manager
Smart Manager Chiller Panel Controller Mini Chiller main board Netware 3 SLM3 NIM FCU main board
Component Component
Technical Training 2007 Technical Training 2007 Technical Training 2007
Smart Manager
Bus Wiring Network Bus Wiring Network
Technical Training 2007 Technical Training 2007 Technical Training 2007
Smart Manager
Chiller Chiller BUS BUS
Chiller Panel 0 Chiller Panel 0 (Master) (Master) Chiller I D 0 Chiller I D 0 Chiller I D 1 Chiller I D 1 Chiller I D 2 Chiller I D 2
CN8 CN8 – – CN8 CN8
Chiller Panel 1 Chiller Panel 1 (Slave) (Slave) Chiller Panel 2 Chiller Panel 2 (Slave) (Slave)
A A B B
Smart Manager
Chiller Bus Chiller Bus
Technical Training 2007 Technical Training 2007 Technical Training 2007
Smart Manager
Smart Manager
Wired Controller (Netware 3) NIM Master NIM Master NIM Master
120 Units of FCU Supply +12 VDC
NI M BUS NI M BUS
Technical Training 2007 Technical Training 2007 Technical Training 2007
FEATURES Fan Coil Unit
- Monitor FCU’s status and control FCU’s settings
(global, group or individual)
- Alarm (6 types of FCU fault)
- Five sets 7 days programmable timer (2 ON/OFF timer)
- 10 Holidays setting (turn OFF all units during holiday
period)
Smart Manager
NI M BUS NI M BUS
Technical Training 2007 Technical Training 2007 Technical Training 2007
Smart Manager
- 120 groups
- Each group must consist one master
- Maximum 16 FCUs in one group including master
- Global Control
- Group control
- Individual control
NI M BUS NI M BUS
Technical Training 2007 Technical Training 2007 Technical Training 2007
Smart Manager
SMART MANAGER
Fan Coil Unit Chiller Settings Go into FCU summary pages to Control and Display status of FCU Go into Chiller summary pages to Control and Display status of Chiller Smart Manager Configuration
Smart Manager Menu Smart Manager Menu
Technical Training 2007 Technical Training 2007 Technical Training 2007
Chiller Summary Pages Smart Manager FCU Summary Pages SM Setting Hold ESC 1s Select “Chiller” Hold ESC 1s Select “Fan Coil Unit” Hold ESC 1s Select “Setting”
Smart Manager
Menu Structure Menu Structure
Technical Training 2007 Technical Training 2007 Technical Training 2007
SM SETTINGS
Priority : FCU Cool Threshold : 50 % Heat Threshold : 50 %
Chiller running mode is determined by FCU status base on threshold value
Set to FCU ,
If one FCU is ON, Chiller turn ON automatically If all FCUs are OFF, Chiller turn OFF automatically
Priority Setting
Manual ON the Chiller will be turn OFF automatically by the setting if all the FCU is OFF
Smart Manager
Smart Manager Setting Smart Manager Setting
Technical Training 2007 Technical Training 2007 Technical Training 2007
SM SETTINGS
Priority : Chiller Cool Threshold : 50 % Heat Threshold : 50 %
Chiller running mode is determined by Chiller status itself
Set to Chiller ,
If Chiller is OFF, No FCU can be turned ON If Chiller turn ON, FCUs can be turned ON or OFF Manual ON the FCU will be turn OFF automatically by the setting
Priority Setting
Smart Manager Setting Smart Manager Setting
Smart Manager
Technical Training 2007 Technical Training 2007 Technical Training 2007
SM SETTINGS
Priority : None Cool Threshold : 50 % Heat Threshold : 50 %
Operation Between Chiller and FCU isolated
Set to None ,
This priority setting is the factory setting
Priority Setting
Smart Manager Setting Smart Manager Setting
Smart Manager
Technical Training 2007 Technical Training 2007 Technical Training 2007
SM SETTINGS
Priority : FCU Cool Threshold : 60 % Heat Threshold : 70 %
Must Set to FCU 50% ≤ Value setting ≤ 100%
- 50
60 70 Cool Threshold (C) 80 70 60
- Heat
Threshold (H) Heating 7 3 cooling 5 5 cooling 4 6 Heating 8 2 6 3
- No. of
FCU in Heat Mode cooling 4 cooling 7 10 Running Mode of Chiller
- No. of FCU
in Cool Mode Total of FCU
If C ≥ 60, Run as Cooling mode (current setting mode) If 40<C<60, remain as the current mode If H ≥ 70, Switch to Cooling Mode Ensure the Running Mode Of Chiller
Smart Manager
Threshold Setting Threshold Setting
Technical Training 2007 Technical Training 2007 Technical Training 2007 Adjust the Dipswitch (DSW2) to assign FCU Unit setting Adjust the Dipswitch (DSW1) to assign Group Address setting
Smart Manager
FCU Unit FCU Unit Addres Addres Setting Setting
Technical Training 2007 Technical Training 2007 Technical Training 2007 CN3 CN3 ~ Connection of NIM Bus to Smart Manager CN1 CN1 ~ Connect to Main Board (WIV3) CN2 CN2 ~ Connect to Wired Controller
Smart Manager
Connection to Smart Manager Connection to Smart Manager
Technical Training 2007 Technical Training 2007 Technical Training 2007
A B A B
Smart Manager
Smart Manager
I nstallation of Smart Manager I nstallation of Smart Manager
Technical Training 2007 Technical Training 2007 Technical Training 2007
Summary Pages Summary Pages Main menu Main menu Setting Menu Setting Menu Timer Menu Timer Menu Operation Menu Operation Menu Alarm Menu Alarm Menu Unit Selection Unit Selection Menu Menu
Press Press ENTER ENTER Press and Press and Hold Hold ENTER ENTER for 1s for 1s Press Press ENTER ENTER
Smart Manager
Menu Structure Diagram for FCU Menu Structure Diagram for FCU
Technical Training 2007 Technical Training 2007 Technical Training 2007
We can control the FCU as :
Global Group Individual
Unit Selection : Unit Selection : Select All Select All Select Group Select Group Select One Select One Display the Global Master (G0U0) status and control all FCUs setting at once Display the Group Master (G1U0) status and control all FCUs setting in that group at once Only display the chosen FCUs and control the FCUs setting
Smart Manager
Unit Selection Menu Unit Selection Menu
Technical Training 2007 Technical Training 2007 Technical Training 2007 Method 1
Unit Selection : Select All Select Group Select One
Press & hold ENTER 1s (in Summary Pages)
01/01/2000 12:00am
Status : OFF Mode : Cool Set Temp : 24 oC Fan : High Room Temp : 27 oC Unit : G0U0 Summary Page Unit : All G1 G0U1 Select the Unit Selection and press ENTER
Smart Manager
Changing Display Unit Changing Display Unit
Technical Training 2007 Technical Training 2007 Technical Training 2007 Method 2
01/01/2000 12:00am
Status : OFF Mode : Cool Set Temp : 24 oC Fan : High Room Temp : 27 oC Unit : G0U0
Press & hold UP or DOWN Key 1s (in Summary Pages) to scroll and display each FCU unit in the network
Unit :
GXUX will keep on changing to show ALL the FCU units exist in the network Let Off the UP or DOWN Key until the GXUX that u wish to display
Smart Manager
Changing Display Unit Changing Display Unit
Technical Training 2007 Technical Training 2007 Technical Training 2007
Press Up and Down Key for page scrolling And Display the Operation Status of FCU
01/01/2000 12:00 am
Status : ON Mode : Cool Set Temp : 24 o C Fan : High Room Temp : 27 oC Unit : G0U0
01/01/2000 12:00 am
Swing : Yes Sleep : No Compressor : OFF Schedule : 1 Timer : Disable
Summary Pages
Smart Manager
FCU Menu Structures FCU Menu Structures
Technical Training 2007 Technical Training 2007 Technical Training 2007
MAI N MENU Operation Menu Setting Menu Timer Menu Alarm Menu Control the Operation
Password Protected Advanced Parameters Setting & Panel Option Clock & Date Setting Timer On/Off Schedule Holiday Off Duration
Record 20 erasable alarm histories
Smart Manager
Main Menu of FCU Main Menu of FCU
Technical Training 2007 Technical Training 2007 Technical Training 2007
01/01/2000 12:00 am Status : ON Mode : Cool Set Temp : 24 o C Fan : High 01/01/2000 12:00 am Swing : Yes Sleep : No Schedule : 1 Timer : Disable
Change the Operation Settings of FCU
Enable or Disable the Timer Schedule Select the Timer Schedule
Smart Manager
Operation Menu Operation Menu
Technical Training 2007 Technical Training 2007 Technical Training 2007
Backlight : Normal Buzzer : ON Screen Saver : Disable Timeout : 5m Contrast : 50% Brightness : Medium Temp Unit : oC Create a “Beeping” sound whenever It trigger any alarm Temperature Unit can be set either
- F or oC
Setting of the Panel itself
Panel Option Panel Option
Smart Manager
Technical Training 2007 Technical Training 2007 Technical Training 2007
MAI N MENU Clock Setting Date Setting Timer Schedules Holiday Set Time: hh mm Set Date: yy mm dd
Timer Menu Timer Menu
Smart Manager
Technical Training 2007 Technical Training 2007 Technical Training 2007
5 sets of programmable timer schedules
SCHEDULE SETTINGS Schedule 1 Schedule 2 Schedule 3 Schedule 4 Schedule 5 Timer 1 Timer 2 ON OFF ON OFF Sun 0800 1600 ----
- Mon 0800 1600 ----
- Tue 0800 1600 ----
- Wed 0800 1600 ----
- 7 days of timer schedule (Sun to Sat)
2 ON/OFF events per day Assigning timer schedule as Global (All FCUs), group (Groups
- f FCU) or individual (one FCU)
Manually On/Off can always override the timer schedule
Timer Schedule Timer Schedule
Smart Manager
Technical Training 2007 Technical Training 2007 Technical Training 2007 After set the 7 days programmable On/ Off Timer in Timer Schedule (up to 5 Sets) Select ONE set of timer schedule in Operation Menu Enable the ‘Timer’ in order to activate the timer schedule
OPERATION MENU Swing : Yes Sleep : No Schedule : 1 Timer : Enable
Assigning ON/ OFF Schedule Assigning ON/ OFF Schedule
Smart Manager
Technical Training 2007 Technical Training 2007 Technical Training 2007
All the FCU and Chiller will be turn OFF Temporally Disable all the timer schedules 10 sets of Holiday Schedules 99 days duration for each holiday FCU can be opened manually ; FCU will switch off at
00:00am for the following day if it still in holiday mode
SCHEDULE SETTINGS Holiday 1 Holiday 2 Holiday 3 Holiday 4 Holiday 5 SCHEDULE SETTINGS Holiday 6 Holiday 7 Holiday 8 Holiday 9 Holiday 10
Holiday Setting Holiday Setting
Smart Manager
Technical Training 2007 Technical Training 2007 Technical Training 2007
Set Holiday 1 Month : 1 Day : 25 Duration : Disable
A sign [H] will be shown in Summary Page during holiday period
Specify the month and date for Holiday starting period Duration for the Holiday is from 1~99 days
How to set a Holiday schedule ?
Holiday Setting Holiday Setting
Smart Manager
Technical Training 2007 Technical Training 2007 Technical Training 2007
Set Holiday 1 Month : 12 Day : 24 Duration : 3
Christmas Holiday : 24/12/10 ~ 26/12/10 Duration : 3 days
Start from 00:00am, 24/12/03 Holiday Mode will be activated Holiday Mode will be deactivated starting from 00:00am, 27/12/03
Example Example
Smart Manager
Technical Training 2007 Technical Training 2007 Technical Training 2007
Faulty or Alarm is triggered An New Alarm or Alarms will pop up
- n the LCD
[G0U0] Alarm 1 Outdoor coil Sensor missing 01/01/00 12:00am
Alarm Alarm
- ccurred Unit
- ccurred Unit
(FCU I D) (FCU I D) Alarm occurred Alarm occurred type type Alarm Alarm
- ccurred time
- ccurred time
Alarm occurred Alarm occurred Date Date “Beeping” sound Backlight blinking
Back To Co Back To Content ntent
Smart Manager
New Alarm Display New Alarm Display
Technical Training 2007 Technical Training 2007 Technical Training 2007
Selection Software
Technical Training 2007 Technical Training 2007 Technical Training 2007
Smart Manager
- Independent Chilled Water FCU
selection software.
- Independent Mini Chiller
selection software.
- McQuay Chilled Water Product
Selection
- Virtual Piping Sizing
Back To Co Back To Content ntent
Technical Training 2007 Technical Training 2007 Technical Training 2007
Competitor’s Product Comparison
Technical Training 2007 Technical Training 2007 Technical Training 2007
Competitor’s Products Comparison
BRIGHT CARRIER DAIKIN OYLM
85HP- 250HP 20HP 13HP 9HP 7HP 5HP 3HP 2HP
M5ACV-CR
Using R410A Refrigerant Using R407C Refrigerant
EWAQ / YQ BHLRCF-Z UWAXP AquaSnap
Product Range
Technical Training 2007 Technical Training 2007 Technical Training 2007
Competitor’s Products Comparison
35.31 12.18 12.96
Volume, ft3
19.68 14.17 18.11
Depth, inch
41.34 46.85 39.76
Width, inch
62.99 31.69 31.10
Height, inch
9.18 8.22 5.12
COP
56 63 59
Noise , dBA
39,238 29,787 33,000
Heating Capacity, BTU/hr
33,096 24,225 27,000
Capacity, BTU/hr
R407C R410A R410A
Refrigerant
BHLRCF-10Z EWYQ007ACV3HP M5ACV030CR
BRIGHT DAIKIN OYLM
3HP
INVERTER MINI CHILLER
Technical Training 2007 Technical Training 2007 Technical Training 2007
Competitor’s Products Comparison
- 35.31
23.13
Volume, ft3
- 27.17
18.11
Depth, inch
- 32.87
39.76
Width, inch
- 57.09
55.51
Height, inch
- 6.59
COP
- 62
Noise Indoor, dBA
- 66,000
Heating Capacity, BTU/hr
- 42,700
50,000
Capacity, BTU/hr
- R407C
R410A
Refrigerant
- UWAXP125AY1
M5ACV055CR
BRIGHT DAIKIN OYLM
5HP
INVERTER MINI CHILLER
Technical Training 2007 Technical Training 2007 Technical Training 2007
Competitor’s Products Comparison
- 35.31
23.13
Volume, ft3
- 27.17
18.11
Depth, inch
- 50.39
39.76
Width, inch
- 57.09
55.51
Height, inch
- 7.75
COP
- 65
Noise Indoor, dBA
- 75,000
Heating Capacity, BTU/hr
- 64,900
70,000
Capacity, BTU/hr
- R407C
R410A
Refrigerant
- UWAXP190AY1
M5ACV075CR
BRIGHT DAIKIN OYLM
7HP
INVERTER MINI CHILLER
Technical Training 2007 Technical Training 2007 Technical Training 2007
Competitor’s Products Comparison
- 35.31
60.07
Volume, ft3
- 27.17
35.43
Depth, inch
- 50.39
59.06
Width, inch
- 57.09
49.61
Height, inch
- 7.92
COP
- 63
Noise Indoor, dBA
- 100,000
Heating Capacity, BTU/hr
- 85,400
95,000
Capacity, BTU/hr
- R407C
R410A
Refrigerant
- UWAXP250AY1
M5ACV100CR
BRIGHT DAIKIN OYLM
9HP
INVERTER MINI CHILLER
Technical Training 2007 Technical Training 2007 Technical Training 2007
Competitor’s Products Comparison
- 70.63
60.07
Volume, ft3
- 27.17
35.43
Depth, inch
- 75.79
59.06
Width, inch
- 59.06
49.61
Height, inch
- 8.36
COP
- 67
Noise Indoor, dBA
- 141,500
Heating Capacity, BTU/hr
- 128,000
131,500
Capacity, BTU/hr
- R407C
R410A
Refrigerant
- UWAXP375AY1
M5ACV135CR
BRIGHT DAIKIN OYLM
13HP
INVERTER MINI CHILLER
Technical Training 2007 Technical Training 2007 Technical Training 2007
Competitor’s Products Comparison
- 93.94
157.36
Volume, ft3
- 27.17
46.93
Depth, inch
- 101.18
82.40
Width, inch
- 59.06
70.32
Height, inch
- 8.97
COP
- 85
Noise Indoor, dBA
- 210,000
Heating Capacity, BTU/hr
- 171,000
200,00
Capacity, BTU/hr
- R407C
R410A
Refrigerant
- UWAXP500AY1
M5ACV210CR
BRIGHT DAIKIN OYLM
20HP
INVERTER MINI CHILLER
Back To Co Back To Content ntent
Technical Training 2007 Technical Training 2007 Technical Training 2007
Thank You Thank You
Back To Co Back To Content ntent