SmartAir Master
The intelligent compressed air management system Developed by Compair to save your customers money
SmartAir Master The intelligent compressed air management system - - PowerPoint PPT Presentation
SmartAir Master The intelligent compressed air management system Developed by Compair to save your customers money Customers will need more Energy Efficient Systems Why do we make more energy efficient compressor and controllers ? Facts
The intelligent compressed air management system Developed by Compair to save your customers money
Page ▪ 2 A Gardner Denver Company
Customers will need more Energy Efficient Systems
▪ Why do we make more energy efficient compressor and controllers ?
▪ Facts aprox 70% of electrical energy is used in Industry
▪ According to Industry figures 10% of all energy used in industry is used to produce compressed air. ▪ By using a controller to run the system more efficiently it is estimated that most systems can reduce there energy consumption on compressed air plants by around 25%.
▪ Your customers are investing in more and more energy saving equipment.
Page ▪ 3 A Gardner Denver Company
SmartAir Conventional system
Target pressure Time Time Process start Process start Pressure Target pressure Pressure
Start-up Compressors can be Pre-defined
Page ▪ 4 A Gardner Denver Company
Required Air System Pressure 7.0 bar ( 101.5 psi ) minimum S A M reduces the pressure band to
LOWER PRESSURE SET POINT UPPER PRESSURE SET POINT
AIR SYSTEM PRESSURE ( BAR g )
8.2 8.0 7.8 7.6 7.4 7.2 7.0 6.8 6.6
WASTED ENERGY WASTED ENERGY WASTED ENERGY
Pressure reduction increased efficiency
On a system with 2 x 75 kW and 1 x 132 = 20 kW reduction
Page ▪ 5 A Gardner Denver Company Air Demand Low High
OPERATION MODE „Energy Saving“
The most inefficient way to run a compressor is off-load. An off load compressor can consume up to 30% of the full load power for zero output. On a 75 kW compressor this could mean off load the total power used could be nearly 30kW The S A M measures the rise and fall of pressure against time, and with the intelligent software, selects the most efficient combination of compressors meet the demand.
Page ▪ 6 A Gardner Denver Company
Innovative: Easy to Specify Easy to Install Easy to Commission Saves Energy and Increases performance Controls up to 12 compressors
Comprehensive status reports The Complete Compressed Air Management System Designed to reduce energy usage
Page ▪ 7 A Gardner Denver Company
Display, Coloured graphic touch panel: 5,7”, resolution QVGA (320x240) Compressor connection via interface RS485
Voltage supply 110V / 230V, 50 / 60Hz, adsorbed power 16 VA
Extension module connection via interface RS485 (max. 4 extension modules) Customer connection via interface RS485: Protocol ModBus RTU, optional PROFIBUS 2 Analogue inputs 4..20mA, 24VDC, max. 500m
Input 1: passive, pressure sensor Input 2: passive / active referring to connection to volume flow sensor
3 Digital inputs max 20m, > 20m coupling relay required 2 Digital outputs, Potential free relay outputs, Rating max. 250V / 1A SD memory card
Page ▪ 8 A Gardner Denver Company
Only few Accessories - easy to select
A Complete package – ready for installation
Page ▪ 9 A Gardner Denver Company
Without Management System With Management System
Large pressure band
Pressure reduction by p = 0,8 bar 3 x L45-7.5 3 x 1.4 kW 4.20 kW 2 x L110-7.5 2 x 5.2 kW 10.40 kW Total power less at 6.7 bar 14.60 kW At 8000 working hours/year Energy saving 116,800 kWh
Cost saving at 0.10 € / kWh 11,680 € / Year
Compressor 1- 5 Pressure Band Control
Compressor 1 Compressor 2 Compressor 3 Compressor 4
Total pressure band
Compressor 5
Pressure- Cascade- Control Small pressure band
7.5 bar 6.5 bar 6.5 bar 6.7 bar
Page ▪ 10 A Gardner Denver Company
SmartAir Master
Compressor 1
L30 L30 L45SR Line pressure sensor RS485-1 Analogue input AI-1
RS485-2 RS485-3
ModBus-RTU PROFIBUS (optional) Customer's PLC to control the air station Selection switch to activate a profile RS485 Dig.inputs Selection switch to activate a profile
Compressor 2 Compressor 3 Receiver Dryer Filter
Dig.input
Connection of: ➢ Compressors ➢ Communication ➢ Air treatment systems
Page ▪ 11 A Gardner Denver Company
ModBus-RTU PROFIBUS module
(100016156)
Webserver module (Visualization)
230V/50-60Hz (ZS1055779) 110V/50-60Hz (ZS1055780)
SmartAir Master (100016136)
Line pressure sensor (100003136) Programmable to different functions (Sensors see Accessoires) 2x2x0,5..1,5m m² twisted pair and screened (100003989) DELCOS Pro GD Pilot DELCOS 1000 Standard or Half/full load compressor Speed regulated compressor (3phase asynchronous motor
Compressor module (STD)
(100016166)
Compressor module (VSD)
(100016222SI M) RS485-3 (Customer) SD card (10001613 8) Digital input DI-1..3 Digital output DO-1..2
Accessoires
Sensors Line pressure sensor 100003136 Volume flow sensor (Kit) ZS1055781 Dew point sensor 100014803 Temperature sensor 100016229 Manuals Programmer guide ModBus-RTU (GB/US) ZS1060126 Programmer guide PROFIBUS (GB/US) ZS1060127 Software update guide ZS1060125 Compressor Connections ZS1061822 Checklist Compressor connections ZS1062760 Miscellaneous SD card reader ZS1069300 Interface Converter USB-RS485 ZS1073178 Interface Converter RS232-RS485 100004858 Keylock Smartair Master ZS1049510
V03Compressor module (STD)
(100016166) SureScan Fixed speed
Compressor module (VSD)
(100016222SIM) +
Connection plug SureScan
(ZS1055047) SureScan-LSR
Extension Module
230V/50-60Hz (100016226) 110V/50-60Hz (100016230) Digital inputs DI-1..8 Digital outputs DO-1..2 Analog inputs AI-1..2 (Sensors see Accesoires)
RS485-2 Analog input AI-1 Analog input AI-2 RS485-1
DELCOS 3100 DELCOS XL GD Pilot MK
Page ▪ 12 A Gardner Denver Company
Metacentre
Not required at SmartAir Master
Connection of CompAir DELCOS
MultiMaster bus DELCOS 3100 DELCOS 3100
DELCOS 3100
Gateway
DELCOS 3100
Gateway
DELCOS 3100
DELCOS 3100
Gateway
SmartAir 5 & 8 /
Page ▪ 13 A Gardner Denver Company
3 digital inputs Standby, no fault Motor running Full load 3 digital outputs Remote load enable Remote Load Remote half / full load
Installation via, DIN rail TS 35, 24-230V UC no coupling relay required 2 plugs RS485 interface LED indication at inputs and outputs
SmartAir Master
Module required for: Delcos 3000, Surescan, Hydrovane, GD & all competitor fixed speed compressor controls
Page ▪ 14 A Gardner Denver Company
4 digital inputs Standby, no fault Motor running On Load Speed
Installation via, DIN rail TS 35, 24-230V UC no coupling relay required 2 plugs RS485 interface LED indication at inputs and outputs
Line pressure sensor compressor
Modulated line pressure
SmartAir Master
Module required for: Delcos3000RS, Quantima, Hydrovane, GD & all competitor variable speed compressor controls
Page ▪ 15 A Gardner Denver Company
Refrigeration dryer, Adsorption dryer, Filter, Condensate Management, etc. Pressure sensor Temperature sensor ( Future development ) 2 relay outputs (programmable)
Supply voltage versions 1.) 230V / 50/60Hz 2.) 110V / 50/60Hz
8 digital inputs 2 analog inputs
SmartAir Master
Page ▪ 16 A Gardner Denver Company
Features: ▪ Latest microprocessor technology ▪ So far in 17 languages available ▪ Intuitive user guidance Benefits: ▪ Easy to use ▪ Comprehensive information ▪ Provides all performance data on a view
Page ▪ 17 A Gardner Denver Company
Commissioning Wizard Features: ▪ Guidance via series of on-screen prompts ▪ Set-up guidance for commissioning engineer ▪ Ensuring the correct settings of parameters Benefits: ▪ Easy and quick installation ▪ Safe and reliable operations ensured ▪ No special training requirements
The GD Pilot Connect is now ready for operation.
GD Pilot Connect
Page ▪ 18 A Gardner Denver Company
Priority 1 Priority 2 Compressor 1 40m³/min Compressor 2 42m³/min Compressor 3 15m³/min Compressor 4 10m³/min Compressor 5 12m³/min A B C D E B A E C D A B D E C
After an adjustable time the SmartAir switches over automaticly the sequence of the compressors.
OPERATION MODE „TIMER ROTATION“
2h A 8h B 11h C 17h D 23h E 51h E 19h A 0h D Compressor 4 48h C 22h B 0h C Compressor 3 40h B 49h D 36h A 26h D 48h E 25h C 0h E 0h B 0h A Compressor 5 Compressor 2 Compressor 1
OPERATION MODE „EQUAL RUNNING HOURS“ The SmartAir will automatically sequence the compressors to maintain equal running hours For installations where the ability to carry out routine planned maintenance on all compressors at the same time is advantageous
Page ▪ 19 A Gardner Denver Company
L37RS Compressor - Specific Power vs Flow
6.0 6.5 7.0 7.5 8.0 8.5 1.0 2.0 3.0 4.0 5.0 6.0 7.0 Free Air Delivery [ m3/min] Specific Total Power [kW/m3/min]
All variable speed compressors working at best operating point
Page ▪ 20 A Gardner Denver Company
▪ Information Menu Overview ▪ Timer Control Overview ▪ Current Profile ▪ Air Station Events ▪ Measured Values ▪ Operating Hours ▪ Statistics ▪ Software (Installed Version)
Page ▪ 21 A Gardner Denver Company
GD Pilot Connect
Page ▪ 22 A Gardner Denver Company
Current line pressure Pressure range Current network demand Compressor status indicator Link to information screens Link to programming screens Current Profile in use Last warning or Alert Current date and time Reset SD Card (used for data logging)
Page ▪ 23 A Gardner Denver Company
Compressor is in standby mode waiting for signal to start. Compressor is on-load but yellow indicates a warning Compressor is in motor start phase. A shutdown has been triggered. Communication error has
between SmartAir Master and this compressor Compressor is
speed machines show loading as a percentage. Compressor is in currently switched off. Compressor is in blow- down phase (start protect active)
Page ▪ 24 A Gardner Denver Company
Instant information on each specific compressor
Service on Events
Page ▪ 25 A Gardner Denver Company
Absolute operation hours of each compressor
Relative operation hours of each compressor
Page ▪ 26 A Gardner Denver Company
Diagrams of line pressure and the compressed air demand
Page ▪ 27 A Gardner Denver Company
Page ▪ 28 A Gardner Denver Company
combination of up to 12 compressors same or different in size, fix speed and variable speedEasy to use TS-GUI (Touch Screen Graphical User Interface)
small pressure band
control
Page ▪ 29 A Gardner Denver Company
size of compressor.
User friendly operation and installation:
(help function)
demand at optimised low pressure band.
High energy saving:
Page ▪ 30 A Gardner Denver Company
SmartAir MASTER Saving Energy