Thermo-mechanical behaviour of Geothermal Energy Pile Dr Rao - - PowerPoint PPT Presentation

thermo mechanical behaviour of geothermal energy pile
SMART_READER_LITE
LIVE PREVIEW

Thermo-mechanical behaviour of Geothermal Energy Pile Dr Rao - - PowerPoint PPT Presentation

Thermo-mechanical behaviour of Geothermal Energy Pile Dr Rao Martand Singh Lecturer (Geotechnical Engineering) Department of Civil & Environmental Engineering 1 Introduction University of Surrey Guildford town, Surrey From


slide-1
SLIDE 1

Thermo-mechanical behaviour of Geothermal Energy Pile

1

Dr Rao Martand Singh

Lecturer (Geotechnical Engineering) Department of Civil & Environmental Engineering

slide-2
SLIDE 2

Introduction

slide-3
SLIDE 3
  • Guildford town, Surrey
  • From London 60 km
  • Close to airports
  • ~ 16,000 students
  • Undergraduate: 12,114
  • MSc: 2,600
  • PhD: 1,005
  • 37% outside the UK
  • Over 95% graduate

employability rate

  • Consistently in top 10
  • Three faculties
  • Faculty of Arts and Social

Sciences

  • Faculty of Health and

Medical Sciences

  • Faculty of Engineering and

Physical Sciences (FEPS)

  • Dept of Civil & Env Eng

University of Surrey

slide-4
SLIDE 4

Wednesday, 22 March 2017 4

Presentation overview

  • Why
  • What
  • How
  • Geothermal Energy Pile: Thermo-Mechanical study
  • Outcome
slide-5
SLIDE 5

Wednesday, 22 March 2017 5

Why

  • 73% energy is being used for

heating/cooling and hot water

  • Every house is responsible for 20,000

kg (20 tonnes) of greenhouse gas emissions (GHG) per year

  • Conventional heating/cooling system

efficiency 50% to 80%

  • Carbon tax, energy is getting more

expensive

  • Reduce energy use and GHG emission

save the world

Average home energy use

slide-6
SLIDE 6

Why

  • According to the International

Energy Agency between 1990 and 2015

– Energy consumption increased by almost 65% – GHG emission increased by 55% – Population increased by 40%

  • Energy use of emerging nations

such as China, India, South Africa, Brazil will exceed by 2020 that for developed nations

Energy consumption, CO2 emissions and world population

(Energy Information Administration, USA 2006)

Developed and emerging nations energy usage

(Energy Information Administration, USA 2006)

slide-7
SLIDE 7

Wednesday, 22 March 2017 7

What is ground energy

  • Ancient concept: caves, underground houses,

wine cellar

  • Ground has stable temperature throughout the

year and it is equal to the average annual temperature

  • Ground is warmer than air in winter and cooler

than air in summer

slide-8
SLIDE 8

Wednesday, 22 March 2017 8

Confusion with terminology

  • Types of geothermal energy

– Deep – Shallow

  • Deep geothermal energy

available at few kms – comes from hot rock due to radioactivity – used for electricity generation

  • Shallow geothermal energy

– under our feet – solar radiation – heating/cooling the buildings

slide-9
SLIDE 9

Wednesday, 22 March 2017 9

How does it work?

  • What do we need?

– Ground – Heat exchanging loop – Heat Pump

  • What is heat exchanging loop?

– Plastic pipe (HDPE) – Fluid (water or water + antifreeze e.g. glycol)

  • Horizontal loop

– Close loop – at 1.5 m – Lot of space available – Trenches – Horizontal directional drillers

  • Vertical loop

– Close loop – Limited space – Vertical Bore hole about 100 m deep

slide-10
SLIDE 10

0.5 m 0.5 m 0.5 m 0.5 m 0.5 m

Back-Hoe Loops

Two-Pipe Four-Pipe Six-Pipe 0.3 m

Trenched Loops

0.5 m Two-Pipe Four-Pipe Extended Slinky

Source: WaterFurnace

Horizontal loop configuration

slide-11
SLIDE 11

Wednesday, 22 March 2017 11

Vertical loop configuration

  • Borehole 100-150 mm diameter
  • U-loop
  • Vertical and Radial direction
  • One or two loops maximum
  • Short circuit
slide-12
SLIDE 12

Open loop GSHP

  • Aquifer
  • if water table is high and stable
  • Beware of ground water flow direction
  • Low installation cost
  • Strict regulations (in some countries it is banned)
slide-13
SLIDE 13

Wednesday, 22 March 2017 13

Heat pump

Image source: Geoexchange

Heating cycle

slide-14
SLIDE 14

Case study

  • Gloucester Police Headquarters, Quedgeley, Gloucester, UK

– Three storey building 8500 m2 – Vertical closed loop – 150 bore holes, 98 m deep – 860 kW Cooling and 765 kW Heating – 9 Reversible heat pumps – Active CO2 Management – Dry Air Cooler on Loop – Completed October 2005 – Energy savings of 36% – Savings of £60,000 per year running cost

Source: GI Energy

slide-15
SLIDE 15

Case study

  • Robert Gordon University, Garthdee Campus, Aberdeen, UK

– New campus located next to river Dee – Aberdeen known as granite city – Granite rock (hard to drill in) – Vertical closed loop – 66 bore holes, 220 m deep – 900kW Cooling and 900 kW Heating – 8 Reversible heat pumps – CoP of 5 for heating and 6 for cooling – Largest commercial GSHP in Scotland – Completed October 2013

Source: GI Energy

slide-16
SLIDE 16

Case study

  • Kingsmill Hospital, Mansfield, Nottinghamshire, UK

– King’s Mill reservoir used for water supply and recreation – Close loop lake system – 140 stainless steel heat exchangers under the surface of the reservoir (hidden by floating reed beds to protect the heat exchangers and new habitat for wildlife) – 42 water source heat pump units – 5.4 MW cooling and 5 MW heating system, largest in Europe – CoP of 6.0 for cooling and 3.8 for heating – Completion Jan 2011 – Temperature difference of 1°C in the vicinity of heat exchangers (requirement of Environment Agency) – Save 9600 MWh of gas and electricity a year – Prevent 1,700 tonnes of CO2 entering into atmosphere which is equivalent to removing 600 cars off the road – Saving of £120,000 a year

Image source: Skanska

slide-17
SLIDE 17

Case study

  • Plas Newydd mansion, Anglesey, Wales, UK

– 300 year old 18th century mansion located next to Menai Strait in Anglesey – Used oil for heating – Used 1500 litres of oil a day during winter (which normal house will use in 10 months) – 300 kW sea (marine) source heat pump (basically WSHP) – Open loop – 200 mm dia pipes run 53 metres to the sea covered by concrete caissons and natural stones – Cost £600,000 – Saving £40,000 per year – Operational since May 2014 – CoP 4.08 and SPF of 2.82

Source: National Trust

slide-18
SLIDE 18

Case study

  • Kingston Heights, Kingston upon Thames, Surrey, UK

– Kingston Heights development next to river Thames – 137 apartments and 145 bedroom hotel. – under-floor heating and hot water – Open loop – Water source heat pump installed 2.5 m under the water surface of river Thames – 2.3 MW heating – Water is abstracted and passed through stainless steel filter fitted with automated backwash system – Two stage filtration system – Second filter system cleans up any silt – No marine life enter into the system – 13 million litres water abstracted per day (equivalent 5 Olympic size swimming pools) – Water fed back into the river and will remain within ±3°C of river temperature – 500 tonnes CO2

Image source: Mitsubishi

slide-19
SLIDE 19

Case studies: Low system maintenance

  • Lochiel Detention Centre, Adelaide, Australia

– 12 heat pumps installed in March 1995 – 3 pump kits at ~£400 each

  • Bureau of Meteorology, Adelaide, Australia

– 3 units installed in September 2002 – 1 Printed Circuit Board and 1 loop flush at ~£375

  • Bandiana Army Headquarters, Wodonga, Victoria, Australia

– 15 units installed in March 1999 – 1 blower electronics at ~£225

  • Mt Barker TAFE, Mt Barker, SA, Australia

– 29 units installed in May 1997 – 1 blower motor at ~£125

  • Geoscience Australia, Jerrabomberra, Canberra, Australia

– 229 units installed in December 1997 – 3 compressors and 5 high pressure switch kits at ~£2000

Source: Geo Exchange

slide-20
SLIDE 20

Wednesday, 22 March 2017 20

What is a Geothermal Energy Pile?

  • What is a Pile?
  • Deep foundation
  • Soft ground
  • High-rise buildings
  • Skin friction and end bearing
slide-21
SLIDE 21

Wednesday, 22 March 2017 21

What is a Geothermal Energy Pile?

  • Vertical loop
  • Cost effective
  • Land
slide-22
SLIDE 22

Wednesday, 22 March 2017 22

Challenges

  • What will happen if heat is transferred in and out of the

pile foundation:

– Pile load capacity (friction) – Surrounding soil bearing capacity – Heat transfer and storage in pile and surrounding soils – Pile expansion, contraction, stress and strain – Soil deformation, consolidation – Does the concrete crack?

slide-23
SLIDE 23

Wednesday, 22 March 2017 23

How to do pile mechanical testing?

Pile static load testing

slide-24
SLIDE 24

Wednesday, 22 March 2017 24

Pile static load testing

slide-25
SLIDE 25

Wednesday, 22 March 2017 25

Pile dynamic load testing

slide-26
SLIDE 26

Wednesday, 22 March 2017 26

Field testing at Monash

  • Static load test using Osterberg cell
  • Thermal loading via heat pump
  • Fully instrumented bore pile

– Vibrating wire strain gages > Vertical and radial strain > Temperature – LVDT > Pile displacement – Thermocouples > Temperature in soil

slide-27
SLIDE 27

Wednesday, 22 March 2017 27

Site for field test

  • Monash University, Clayton
slide-28
SLIDE 28

Wednesday, 22 March 2017 28

Pile installation

slide-29
SLIDE 29

Wednesday, 22 March 2017 29

Schematic of field pile

slide-30
SLIDE 30

Wednesday, 22 March 2017 30

Thermo-Mechanical testing

  • Short term thermal loading

– Heated (2.4 KW) for 9 days – Cooled for 47 days

  • Long term thermal loading

– Heated (2.4 KW) for 52 days – Cooled for 78 days

  • Pile tested using O-cells before and after each heating and

cooling cycle to investigate the effect of heating/cooling on pile load capacity.

slide-31
SLIDE 31

Wednesday, 22 March 2017 31

Results

  • Initial Ground temperature measured in the borehole
slide-32
SLIDE 32

Wednesday, 22 March 2017 32

Results

  • Fluid temperature short term heating test
slide-33
SLIDE 33

Wednesday, 22 March 2017 33

Results

  • Pile temperature short term heating test (a) transient (b) thermal profile
slide-34
SLIDE 34

Wednesday, 22 March 2017 34

Results

  • Pile load capacity does not get affected by heating/cooling of energy pile
  • Instead pile load capacity increased after heating