1 Control Strategies 2009 Arrow Canyon Complex Air Cooled Condenser 2 Harry Allen Arrow Canyon Complex Site Chuck Lenzie Silverhawk Canyon Complex Arrow 3 Chuck Lenzie Canyon Complex Arrow Control I ssues Arrow Canyon Complex


slide-1
SLIDE 1

1

Arrow Canyon Complex Air Cooled Condenser Control Strategies 2009

slide-2
SLIDE 2

Arrow Canyon Complex Site

2 Arrow Canyon Complex

Harry Allen Chuck Lenzie Silverhawk

slide-3
SLIDE 3

Chuck Lenzie

3 Arrow Canyon Complex

slide-4
SLIDE 4

Control I ssues

4 Arrow Canyon Complex

Start-Up Operations Fan Sequencing Normal Operations Fan Sequencing High Winds

slide-5
SLIDE 5

Configuration

5 Arrow Canyon Complex

Steam Flow

Block 2 Block 1

slide-6
SLIDE 6

Configuration

6 Arrow Canyon Complex

Fan Street Steam Flow

Non-Condensable Gases Condensate

E D C B A

slide-7
SLIDE 7

Configuration – Fan Streets

7 Arrow Canyon Complex

Fan Cell Address

E D C B A E D C B A E D C B A E D C B A

slide-8
SLIDE 8

Configuration – Fan Sequence

8 Arrow Canyon Complex

First, the Center, C Row, Slow then Fast, Then B, D, A & E Slow, then Fast

slide-9
SLIDE 9

Control I ssues – Start-Up

9 Arrow Canyon Complex

Currently S/U only Available in Manual

Mode

– During S/U Operators sometime forget to put in manual.

Too Many Fans

– Causes Vacuum Problems.

Exploring Automating the Start-up

slide-10
SLIDE 10

Configuration

10 Arrow Canyon Complex

Proposed New Fan Starting Sequence:

First, the Center, C Row, Slow then Fast, Then B, D, A & E Slow, then Fast

slide-11
SLIDE 11

Control I ssues – Wind

11 Arrow Canyon Complex

Currently Only One Sequence.

– Off Summer Peak, not fans run. – Windward Edge Fans have diminished efficiency.

Consider Changing Sequence Based on

Wind.

– Explore Staging On Windward Fans Last.

slide-12
SLIDE 12

Temperature Plot – Wind from

SW @ ~ 15MPH, OSA Temp 94°F, All Fans in Fast

12 Arrow Canyon Complex A B C D E 5.0 7.0 9.0 1.0 3.0 301 302 303 304 305 306 307 308 309 310 401 402 403 404 405 406 407 408 409 410 103.0-104.0 101.0-103.0 99.0-101.0 97.0-99.0 95.0-97.0

slide-13
SLIDE 13

Temperature Plot – Wind from

NE @ ~ 15MPH, OSA Temp 102°F, All Fans in Fast

13 Arrow Canyon Complex A B C D E 4.0 6.0 8.0 0.0 2.0 4.0 6.0 8.0 0.0 2.0 4.0 301 302 303 304 305 306 307 308 309 310 401 402 403 404 405 406 407 408 409 410 122.0-124.0 120.0-122.0 118.0-120.0 116.0-118.0 114.0-116.0 112.0-114.0 110.0-112.0 108.0-110.0 106.0-108.0 104.0-106.0

slide-14
SLIDE 14

Control I ssues – Wind

14 Arrow Canyon Complex

Initial Temperature Survey Found

Little Cell Temperature to Wind Correlation.

Not sure if this issue worth pursuing at

Chuck Lenzie.

slide-15
SLIDE 15

Questions

15 Arrow Canyon Complex